BWL Standard 2 Part Industrial Gland
 

    APPLICATION  

   Single wire armoured cable types.   
  Dry Indoors.

   FITTING INSTRUCTIONS

  1. Seperate gland into its two component       parts and pass item 2over the cable.
  2. Strip back outer sheath and armour to       suit equipment geometry.
  3. Expose armouring by further stripping       outer sheath for a length equivalent to       the item 1 knurl plus 5mm.
  4. Secure Item 1 into the equipment.
  5. Pass cable through item 1, equally       spacing armoured wires on knurled       cone.
  6. Lock armouring by tightening item 2
      onto item 1.
  


See dimensions table below
Gland
Size
Entry Thread
Dia.     
   Min    
    
'C'     Length 'D' 
Bore
Dia.
'A'
Bore
Dia.
'B'
Armor
Wire
Dia.
Length
'E'
Envelope
Dia.
'F'
Shroud
Ref.
20/16
20
15
8.7
13.5
0.9
26.5
24.5
159
20S
20
10
11.7
16.0
0.9/1.25
28.5
27.0
160
20
20
10
14.0
21.0
0.9/1.25
32.5
33.5
162
25
25
10
20.0
27.5
1.25/1.60
35.5
40.0
163
32
32
10
26.3
34.0
1.60/2.00
35.5
51.0
164
40
40
15
32.2
40.5
1.60/2.00
38.0
56.5
165
50S
50
15
38.2
46.8
2.00/2.50
38.5
66.5
166
50
50
15
44.1
53.2
2.00/2.50
39.5
79.0
167
63
63
15
56.0
65.9
2.50
51.5
89.0
168
75S
75
15
62.0
72.0
2.50
60.5
100.0
169
75
75
15
68.0
78.6
2.50
57.5
111.5
170
90
90
15
79.4
90.5
2.50/3.15
68.0
129.0
171