Pliable
wire armoured cable types.. Indoors
or outdoors
(internal and external moisture).
APPLICABLE STANDARD
Designed to BS 6121.
Certified to BS 4683 (Part 2) and
BS 5501 (Part 5)
FLP Certificate No. 865014 U (Gp.1)
FITTING INSTRUCTIONS
1.
Seperate gland into three main component parts
by seperating items
4, 5 and 6.
2. Ensure the seal is in its relaxed state
and pass item 6 and 5 over
the cable. Note: Item 5 must
be correctly oriented.
3. Strip back outer sheath and armour to suit
equipment geometry.
4. Expose armouring by further stripping outer
sheath for a length equivalent to the
item 4 knurl plus 5mm.
Secure Item 1 into the equipment.
5. Ensure seal (item 2) is in its relaxed state (but
do not seperate items 1
and 4) Secure Item 1 into
the
equipment.
6. Pass cable through combinations of items
1 - 4, equally spacing the armouring
over the knurled cone.
7. Whilst continuing to push cable forward
to maintain armour wires
in contact with the knurled
cone, tighten item 4 into item
1.
8. Lock armouring by pushing item 5 over the
armouring and tightening item 6
onto item 4. Note: Items 4 and
6 should not lock
face to face.
9. Close vottom seal by tightening second hexagon
of item 6.
See dimensions
table below
Gland
Size
Thread
Entry
Dia. 'C'
Length
Metric Imp 'D' Min.
Entry
seal Closure Range Max.'A'
Min.
Bottom
Seal Closure
Range
Max 'B' Min
Length
'E'
Max.
Envelope
Dia.
'F'
Pliable
Wire strands/dia.
Shroud
Ref.
20S
20
3/4"
15
11.7
- 5.9
16.0
- 11.2
70.0
30.5
7/0.45
161
20
20
3/4"
15
14.0
- 6.4
21.0
- 13.2
68.0
33.5
7/0.45
162
25S
25
1"
15
20.0
- 10.0
24.0
- 15.5
78.0
40.0
7/0.45
163
25
25
1"
15
20.0
- 10.0
27.5
- 22.5
78.0
40.0
7/0.45
163
32
32
1
1/4"
15
26.3
- 19.0
34.0
- 26.4
78.0
51.5
7/0.45
- 0.71
164
40
40
1
1/2"
15
32.2
- 25.0
40.5
- 31.5
82.0
61.5
7/0.71
165
For
Spigot and flange bolting See Adaptor Flange Data
Sheet. DETAILS
OF LARGER SIZES (UP TO 75mm) - ON REQUEST
All Dimensions in millimetres unless shownotherwise.