1.
Seperate gland into its two component parts
and pass item 2 over the cable.
2. Strip back outer sheath and armour to suit
equipment geometry.
3. Expose armouring by further stripping outer
sheath for a length equivalent to the
item 1 knurl plus 5mm.
4. Secure Item 1 into the equipment.
5. Pass cable through item 1, equally spacing
armoured wires on knurled cone.
6. Lock armouring by tightening item 2
onto item 1. Note: Item 1 and
Item 2 should not
lock face to face.
See dimensions
table below
Gland
Size
Thread
Entry
Dia. 'C'
Length
Metric Imp 'D' Min.
Entry
seal Closure Range Max.'A'
Min.
Bottom
Seal Closure
Range
Max 'B' Min
Length
'E'
Max.
Envelope
Dia.
'F'
Armour
Wire
Dia.
Shroud
Ref.
20S
20
3/4"
15
11.7
- 5.9
16.0
- 11.2
70.0
30.5
0.9
/ 1.25
161
20
20
3/4"
15
14.0
- 6.4
21.0
- 13.2
68.0
33.5
0.9
/ 1.25
162
25S
25
1"
15
20.0
- 10.0
24.0
- 15.5
78.0
40.0
1.25
/ 1.60
163
25
25
1"
15
20.0
- 10.0
27.5
- 22.5
78.0
40.0
1.25
/ 1.60
163
32
32
1
1/4"
15
26.3
- 19.0
34.0
- 26.4
78.0
51.5
1.60
/ 2.00
164
40
40
1
1/2"
15
32.2
- 25.0
40.5
- 31.5
82.0
61.5
1.60
/ 2.00
165
For
Spigot and flange bolting See Adaptor Flange Data
Sheet. DETAILS
OF LARGER SIZES (UP TO 75mm) - ON REQUEST
All Dimensions in millimetres unless shownotherwise.